Navien · Air handler troubleshooting

Leak sensor: blower runs and outdoor unit stays off, no leak

Navien NAM

What is going on

The coil's leak detection system is in mitigation mode with no leak.

Likely causes

  • Real refrigerant leak at the coil
  • Sensor failed or at end of life
  • Sensor wiring damaged or unplugged
  • Sensor plug pointing up and full of water (except Cubic sensors)

Check in this order

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Check for a leak with a portable detector first.
  3. In mitigation the indoor blower runs and the 24 V to the outdoor contactor is opened. The blower runs until 5 minutes after the gas level drops below the sensor setpoint.
  4. Check the sensor harness plugged in, not damaged, plug pointing down or sideways.
  5. No leak and the system stays in mitigation: replace the sensor with a Navien-approved one. An adapter harness may come with it.
  6. Run the verification test after the repair.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, 4. Refrigerant Leak Detection System, sequence of operation and sensor replacement p.20-23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.