Navien · Air handler troubleshooting

Hydronic model: no control power on the hydronic board

Navien NAS

What is going on

Hydronic heat models run on 115 V with a hydronic control board.

Likely causes

  • No 115 V supply
  • Board fuse blown

Check in this order

  1. Check 115 VAC between L1 and N on the power terminal block (or pins 4 and 5 of the motor power plug).
  2. Check 115 VAC between XFMR and N/L2 on the board.
  3. Check 24 VAC between Rin and COM, then between R and COM.
  4. 24 VAC on Rin but not on R the board fuse is blown.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.