Hydronic model: no control power on the hydronic board
What is going on
Hydronic heat models run on 115 V with a hydronic control board.
Likely causes
- No 115 V supply
- Board fuse blown
Check in this order
- Check 115 VAC between L1 and N on the power terminal block (or pins 4 and 5 of the motor power plug).
- Check 115 VAC between XFMR and N/L2 on the board.
- Check 24 VAC between Rin and COM, then between R and COM.
- 24 VAC on Rin but not on R the board fuse is blown.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.