Navien · Air handler troubleshooting

Hydronic model: blower motor not running

Navien NAS

What is going on

Motor checks on hydronic heat models (ECM or constant torque).

Likely causes

  • No 115 V at the motor
  • No 24 V call from the thermostat
  • Loose motor plugs
  • ECM board fault
  • Failed motor

Check in this order

  1. Check 115 VAC between L1 and N (or motor plug pins 4 and 5). Restore power if missing.
  2. ECM motor check 24 VAC C1 to W1 (heat) or C1 to G (cooling / fan) on the ECM board. Missing: check thermostat and wiring.
  3. ECM signals present do the ECM board pin checks, then replace the motor or motor module.
  4. Constant torque motor check 24 VAC from COM/24V to HI, MED or LO on the board with a call.
  5. 115 V at the motor and 24 V on a tap but no motor: check the motor terminals and BMMP/BMFP plugs, then replace the motor.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.26-27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.