Navien · Air handler troubleshooting
Hydronic model: blower motor not running
What is going on
Motor checks on hydronic heat models (ECM or constant torque).
Likely causes
- No 115 V at the motor
- No 24 V call from the thermostat
- Loose motor plugs
- ECM board fault
- Failed motor
Check in this order
- Check 115 VAC between L1 and N (or motor plug pins 4 and 5). Restore power if missing.
- ECM motor check 24 VAC C1 to W1 (heat) or C1 to G (cooling / fan) on the ECM board. Missing: check thermostat and wiring.
- ECM signals present do the ECM board pin checks, then replace the motor or motor module.
- Constant torque motor check 24 VAC from COM/24V to HI, MED or LO on the board with a call.
- 115 V at the motor and 24 V on a tap but no motor: check the motor terminals and BMMP/BMFP plugs, then replace the motor.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.26-27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.