Daikin · Air handler troubleshooting
Heating emergency mode for EEV cased coil with gas furnace or modular blower
What is going on
Temporary heat only, used when communication wiring or the thermostat has failed and cannot be fixed right away. The gas furnace or modular blower runs the heat alone without a thermostat. It does not hold a set room temperature.
Likely causes
- Broken or damaged communication wires
- Failed thermostat
- Outdoor unit or indoor unit communication errors (E51, Ed2, E76, E77, E78)
Check in this order
- Turn off power to all equipment before setting or wiring.
- Remove the thermostat communication wires (1, 2, R and C) from every connected unit: EEV cased coil, gas furnace or modular blower, outdoor unit and thermostat.
- Short-circuit the communication terminals of the gas furnace or modular blower with the wires. Use the furnace or blower service manual for the correct points.
- On the EEV cased coil control board, set switch bank DS-6: S-21 to OFF and S-22 to ON.
- Turn power on. Heating emergency mode starts automatically.
- Make sure the outdoor unit is stopped. No dip switch change is needed on the outdoor unit.
- When communication is restored, set the dip switches back to default and reconnect all thermostat communication wires.
Applies to: EEV cased coil with gas furnace or modular blower
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SiUS612209EA service instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.