Daikin · Air handler troubleshooting
Heating emergency mode - EEV air handler electric heat
What is going on
Runs the electric heat strips with no thermostat, in High or Low heat level. The cycle timing is in the sequence entry for this mode. Outdoor unit must stay stopped during this mode.
Check in this order
- Set DS-3 S-9 to S-12 to match the installed heater kit size using the heater kit table.
- On the indoor control board DS-6, set S-21 and S-22 for the heat level: S-21 OFF and S-22 ON for High heat level; S-21 ON and S-22 ON for Low heat level. Default is both OFF.
- If the control board shows an Ed error on startup, the DS-3 heater kit DIP settings do not match the kit. Correct them to clear the error.
- Once communication is re-established, set DS-6 S-21 and S-22 back to OFF (normal operation).
Applies to: DFVE EEV air handler with electric heater kit
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.