Daikin · Air handler troubleshooting

Emergency heating mode for EEV cased coil with gas furnace or modular blower

DV**FECDFVE**CAPE(A)*CHPE*

What is going on

Use only as a temporary fix when wiring or the thermostat cannot be corrected at once. The gas furnace or modular blower runs the electric heat without the thermostat. Emergency mode does not hold a room set point. Acceptable when the outdoor unit shows E51 or Ed2, or the EEV indoor unit shows E76, E77 or E78. Cycling power may clear codes without fixing the cause.

Check in this order

  1. Turn off power to all equipment before setting or wiring.
  2. Remove the thermostat communication wires (1, 2, R and C) from all connected equipment (EEV cased coil, gas furnace or modular blower, outdoor unit and thermostat).
  3. Short-circuit the communication terminal of the gas furnace or modular blower with the wires so it runs alone in heating emergency mode. Check the furnace or blower service manual for the connection points.
  4. Set the EEV cased coil dip switches S-21 to OFF and S-22 to ON on switch bank DS-6.
  5. Turn on power. Heating emergency mode starts. The outdoor unit must stay off during this mode. No dip switch change is needed in the outdoor unit.
  6. When communication is restored, set the dip switches back to default and restore all thermostat communication wires.

Applies to: EEV cased coil with gas furnace or modular blower

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.