Navien · Air handler troubleshooting

Electric heat strip not heating

Navien NAS

What is going on

Blower runs but the electric heat does not warm the air.

Likely causes

  • Open heating element
  • Open limit control
  • Failed heater contactor

Check in this order

  1. Check 208-240 VAC across contactor load terminals T1 and T2.
  2. Voltage present power off and ohm the element. Open (infinite) = replace the element.
  3. No voltage on T1/T2 but voltage on L1/L2 check for an open limit and replace it.
  4. No voltage on T1/T2, voltage on L1/L2 and 24 VAC on the contactor coil: replace the contactor.
  5. 5 kW = 1 element, 10 kW = 2, 15 kW = 3 (two top, one bottom), 20 kW = two assemblies. Models up to 10 kW have one contactor, 15 and 20 kW have two.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.25-26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.