Navien · Air handler troubleshooting
Electric heat strip not heating
What is going on
Blower runs but the electric heat does not warm the air.
Likely causes
- Open heating element
- Open limit control
- Failed heater contactor
Check in this order
- Check 208-240 VAC across contactor load terminals T1 and T2.
- Voltage present power off and ohm the element. Open (infinite) = replace the element.
- No voltage on T1/T2 but voltage on L1/L2 check for an open limit and replace it.
- No voltage on T1/T2, voltage on L1/L2 and 24 VAC on the contactor coil: replace the contactor.
- 5 kW = 1 element, 10 kW = 2, 15 kW = 3 (two top, one bottom), 20 kW = two assemblies. Models up to 10 kW have one contactor, 15 and 20 kW have two.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.25-26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.