Daikin · Air handler troubleshooting

ECM motor winding check

DFVEDV**FEC

What is going on

Checks the three motor phase windings for balance and for shorts to the motor shell.

Likely causes

  • Unequal or open phase windings
  • Phase winding shorted to motor shell

Check in this order

  1. Disconnect power and wait 5 minutes for capacitors to discharge.
  2. Disassemble the motor as in the control/end bell steps.
  3. At the 3-circuit motor harness, measure resistance between each phase winding. Readings should be equal.
  4. Replace the motor if readings are unequal, open, or shorted.
  5. Measure resistance between each phase winding and the motor shell. Replace the motor if any winding is shorted to the shell.
  6. Reassemble and reinstall the blower assembly.

Applies to: ECM blower motor windings

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.