Daikin · Air handler troubleshooting
ECM motor test with UltraCheck-EZ tool
What is going on
The UltraCheck-EZ diagnostic tool runs the ECM motor to show whether the motor and control/end bell are working. Its fuse is not replaceable and the tool must only be connected to 24 VAC.
Likely causes
- Motor control/end bell fault
- Motor fault
- Tool not getting 24 VAC
Check in this order
- Disconnect power to the indoor unit.
- Unplug the 4-circuit control harness from the motor.
- Plug the 4-circuit connector from the tool into the motor control connector.
- Connect one alligator clip to a ground source and the other to a 24 VAC source (clips are not polarized).
- Turn power on to the indoor unit.
- Press the orange power button to send a run signal. Allow up to 5 seconds for the motor to start.
- If the orange button does not light, the tool fuse is open or the tool is not on 24 VAC.
- Read the green LED and the motor action. Blinking LED with rotating motor means the motor and control/end bell are good. LED off with rotating motor means replace the control/end bell. Blinking LED with motor not rotating means check the motor. LED off with motor not rotating means replace the control/end bell and verify the motor.
- Press the orange button to stop the motor, disconnect power and the tool, then reconnect the 4-wire harness.
Applies to: Emerson ECM blower in indoor air handler
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.