Daikin · Air handler troubleshooting
ECM high voltage power circuit checks
What is going on
Checks the line voltage feed to the ECM motor from the 5-circuit power connector.
Likely causes
- No supply voltage to indoor unit
- Open wiring in the 5-circuit power harness
Check in this order
- Disconnect power to the indoor unit.
- Unplug the 5-circuit power connector to the ECM motor.
- Turn power on to the indoor unit.
- Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
- Measure voltage between pins 4 and 3, then between pins 5 and 3. Each should be about half the reading from step 4.
- If no voltage is present, check supply voltage to the indoor unit (see S-1).
- Disconnect power, then reconnect the 5-circuit harness.
Applies to: ECM blower in indoor air handler
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.