Daikin · Air handler troubleshooting

ECM high voltage power circuit checks

DV**FECDFVE**

What is going on

Checks the line voltage feed to the ECM motor from the 5-circuit power connector.

Likely causes

  • No supply voltage to indoor unit
  • Open wiring in the 5-circuit power harness

Check in this order

  1. Disconnect power to the indoor unit.
  2. Unplug the 5-circuit power connector to the ECM motor.
  3. Turn power on to the indoor unit.
  4. Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
  5. Measure voltage between pins 4 and 3, then between pins 5 and 3. Each should be about half the reading from step 4.
  6. If no voltage is present, check supply voltage to the indoor unit (see S-1).
  7. Disconnect power, then reconnect the 5-circuit harness.

Applies to: ECM blower in indoor air handler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.