Daikin · Air handler troubleshooting

ECM high voltage power circuit check

DFVEDV**FEC

What is going on

Checks the line voltage feed to the ECM motor power connector with the 5-circuit harness unplugged.

Likely causes

  • No supply voltage to the indoor unit
  • Open harness or connector

Check in this order

  1. Disconnect power to the indoor unit.
  2. Unplug the 5-circuit power connector at the ECM motor.
  3. Turn on power to the indoor unit.
  4. Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
  5. Measure voltage between pins 4 and 3. It should be about half the step 4 voltage.
  6. Measure voltage between pins 5 and 3. It should be about half the step 4 voltage.
  7. If no voltage is present, check supply voltage to the indoor unit.
  8. Disconnect power, then reconnect the 5-circuit harness.

Applies to: ECM motor 5-circuit power connector

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.