Daikin · Air handler troubleshooting
ECM high voltage power circuit check
What is going on
Checks the line voltage feed to the ECM motor power connector with the 5-circuit harness unplugged.
Likely causes
- No supply voltage to the indoor unit
- Open harness or connector
Check in this order
- Disconnect power to the indoor unit.
- Unplug the 5-circuit power connector at the ECM motor.
- Turn on power to the indoor unit.
- Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
- Measure voltage between pins 4 and 3. It should be about half the step 4 voltage.
- Measure voltage between pins 5 and 3. It should be about half the step 4 voltage.
- If no voltage is present, check supply voltage to the indoor unit.
- Disconnect power, then reconnect the 5-circuit harness.
Applies to: ECM motor 5-circuit power connector
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.