What is going on

Use this when the ECM motor control is suspected. The control/end bell has an NTC thermistor and large capacitors.

Likely causes

  • Cracked NTC thermistor
  • Bulging or swollen capacitors
  • Low insulation resistance at the 3-circuit connector

Check in this order

  1. Disconnect power and wait 5 minutes for the motor capacitors to discharge.
  2. Disconnect the motor control and motor power harnesses.
  3. Remove the blower assembly from the indoor unit.
  4. Remove the three screws holding the control/end bell to the motor and disconnect the 3-circuit harness.
  5. Inspect the NTC thermistor. Replace the control/end bell if it is cracked or broken.
  6. Inspect the large capacitors. Replace the control/end bell if any are bulging or swollen.
  7. With an ohmmeter, check resistance between each terminal of the 3-circuit connector. 1 MΩ or greater is good. Replace the control/end bell if below 1 MΩ.
  8. Reassemble in reverse order and reinstall the blower assembly.

Applies to: ECM motor control/end bell

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.