Daikin · Air handler troubleshooting
ECM control/end bell check
What is going on
Use this when the ECM motor control is suspected. The control/end bell has an NTC thermistor and large capacitors.
Likely causes
- Cracked NTC thermistor
- Bulging or swollen capacitors
- Low insulation resistance at the 3-circuit connector
Check in this order
- Disconnect power and wait 5 minutes for the motor capacitors to discharge.
- Disconnect the motor control and motor power harnesses.
- Remove the blower assembly from the indoor unit.
- Remove the three screws holding the control/end bell to the motor and disconnect the 3-circuit harness.
- Inspect the NTC thermistor. Replace the control/end bell if it is cracked or broken.
- Inspect the large capacitors. Replace the control/end bell if any are bulging or swollen.
- With an ohmmeter, check resistance between each terminal of the 3-circuit connector. 1 MΩ or greater is good. Replace the control/end bell if below 1 MΩ.
- Reassemble in reverse order and reinstall the blower assembly.
Applies to: ECM motor control/end bell
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.