Daikin · Air handler troubleshooting

ECM control/end bell and motor winding checks

DV**FECDFVE**

What is going on

Tests the control/end bell and motor windings after the blower assembly is removed. The motor contains capacitors that hold a charge for several minutes.

Likely causes

  • Cracked or broken NTC thermistor in the control/end bell
  • Bulging or swollen capacitors
  • Low resistance in the control/end bell connector
  • Unequal, open or shorted motor windings

Check in this order

  1. Disconnect power and wait 5 minutes for the capacitors to discharge.
  2. Disconnect the motor control and motor power harnesses, then remove the blower assembly.
  3. Remove the three screws holding the control/end bell to the motor and disconnect the 3-circuit harness.
  4. Inspect the NTC thermistor. Replace the control/end bell if cracked or broken.
  5. Inspect the large capacitors. Replace the control/end bell if any are bulging or swollen.
  6. Check resistance between each terminal of the 3-circuit connector. Replace the control/end bell if resistance is lower than 1 MΩ.
  7. For the motor, measure resistance between each phase winding with an ohmmeter. Replace the motor if the readings are unequal, open or shorted.
  8. Measure resistance between each phase winding and the motor shell. Replace the motor if any winding is shorted to the shell.
  9. Reassemble in reverse order and replace the blower assembly in the air handler or modular blower.

Applies to: Emerson ECM blower in indoor air handler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.