Viessmann · Heat pump
E20 Exhaust temperature overprotection
What the control is telling you
Compressor exhaust (discharge) temperature is too high, so the unit shuts down to protect itself.
Applies to: Vitocal 100-AW AM2V outdoor unit
Likely causes
- Lack of refrigerant in the system
- Scaling of casing or plate heat exchanger
- Fin frosting is serious
- Fins dirty and blocked, ventilation poor
- Abnormal throttling
- Outlet water temperature on the high side
- System blockage
Test and repair steps
- Connect a pressure gauge and check refrigerant pressure during shutdown; if it reads 0, refrigerant has leaked out.
- Check for leaks with a leak detector and repair any leak found.
- If no leak, check compressor current and inlet/outlet water temperature difference after start-up; evacuate, recharge and restart if these are low.
- Check the heat exchanger inlet and outlet for scaling; descale if serious.
- Check for heavy frost on the fins and try a manual defrost; adjust defrost settings if needed.
- Clean the fins and make sure the air return path is clear.
- Check the electronic expansion valve coil and body for firm mounting and a good connection to the main board.
- Knock the expansion valve body and restart; if heating runs normally, the valve was stuck.
- Compare the water temperature sensor reading with the actual water temperature; replace or relocate the sensor if it reads much lower.
- Recover refrigerant, remove and inspect the filter, and replace it if blocked, then run a trial.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal 100-AW AM2V installation, service and operating instructions, p. 74. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.