Viessmann · Heat pump
E16 Low pressure protection
What the control is telling you
Low refrigerant pressure protection has tripped. Causes include a refrigerant leak, a faulty low pressure switch, poor defrost, dirty fins, poor throttling, or a blocked system.
Applies to: Vitocal 100-AW AM2V outdoor unit
Likely causes
- Refrigerant leak
- Bad connection or damaged low pressure switch
- Poor defrosting
- Dirty or blocked fins with poor ventilation
- Abnormal throttling
- System blockage
Test and repair steps
- Connect a pressure gauge and read refrigerant pressure at shutdown. A reading of zero means refrigerant has leaked out.
- Find and repair any leak with a leak detector. If none, check compressor current and inlet/outlet water temperature difference after start-up, then re-evacuate and recharge to the nameplate amount.
- Check the low pressure switch connection and replace the switch if damaged.
- Perform a manual defrost. If the unit runs normally afterwards, adjust defrost parameters (shorter heating cycle, longer defrost time, higher set water temperature).
- Clean the fins to remove dirt and debris.
- Check the electronic expansion valve coil and body are secure and the coil is connected correctly. Tap the valve body and restart. Replace the coil or valve body if it is stuck or faulty.
- Recover refrigerant, remove the filter and check for blockage. Clean or replace the filter.
- If the fault remains, contact a professional technician.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 71. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.