Viessmann · Heat pump
E19 Electric heating overload protection
What the control is telling you
Electric backup heater overload protection has tripped. Causes include the heater running without water, low water flow, or a faulty or miswired overload switch.
Applies to: Vitocal 100-AW AM2V electric backup heater
Likely causes
- Electric heater running without load
- Insufficient water flow
- Overload protection switch wrongly connected or damaged
- Jumper on the electric heater overload terminal strip wrongly connected
Test and repair steps
- Check that the water system is full of water.
- Check the water flow. If it is low, follow the water flow protection (E18) steps.
- With the unit off, check the overload switch is closed. If open, check the wiring. If wiring is correct, replace the overload switch.
- Tighten the overload switch wiring or replace the electric heater assembly if needed.
- If the switch is closed, contact a professional technician.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 72. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.