Viessmann · Heat pump
E18 Water flow protection
What the control is telling you
Water flow is too low or the flow switch has tripped. Causes include a faulty pump, trapped air, high water resistance, closed valves, a dirty filter or a faulty flow switch.
Applies to: Vitocal 100-AW AM2V water circuit
Likely causes
- Water pump failure
- Air trapped in the water system
- High water circuit resistance
- Water system valves not fully open
- Dirty or blocked water circuit filter
- Water flow switch wrongly connected or damaged
Test and repair steps
- Check the water pump runs and that its indicator light is normal.
- Open the high point exhaust valve and vent the system until no gas comes out.
- Check the water circuit length and fittings. If resistance is too high, add a secondary pump.
- Confirm all water system valves that should be open are open.
- Clean the water circuit filter.
- Check the flow switch wiring and that its contact closes and opens correctly with a multimeter. Replace the switch if it is stuck on or off.
- If the fault remains, contact a professional technician.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 72. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.