Viessmann · Heat pump
E14 High pressure protection
What the control is telling you
High refrigerant pressure protection has tripped. Causes include a faulty or wrongly wired high pressure switch, scaled heat exchanger, dirty or blocked fins, poor throttling, high outlet water temperature, or refrigerant overcharge.
Applies to: Vitocal 100-AW AM2V outdoor unit
Likely causes
- High pressure switch damaged or wrongly connected
- Scaling in the casing or plate heat exchanger
- Dirty or blocked fins with poor airflow
- Abnormal throttling (electronic expansion valve)
- Outlet water temperature too high
- Refrigerant overcharge
Test and repair steps
- With a multimeter, check the high pressure switch is closed 3 minutes after shutdown. If open, check its wiring. If still open, replace the switch.
- Check the heat exchanger inlet and outlet for scaling. Have a professional clean the heat exchanger if scaling is heavy.
- Check the fin return air path for blockage and clean the fins.
- Change the electronic expansion valve opening and watch high/low pressure, suction and discharge temperatures. Replace the valve or coil if there is no change.
- Check the set temperature against the outlet water temperature before the fault. Insulate the sensor with thermal silicone and a sleeve if the outlet reading is more than 4 LF (2 LC) low.
- If condensing temperature minus refrigerant evaporating temperature is above 10 °C (50 °F), re-evacuate, hold pressure and recharge to the nameplate amount.
- If no fault is found, contact a professional technician.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 70. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.