Viessmann · Heat pump
E26 Outlet water over heat
What the control is telling you
Outlet water temperature is too high.
Applies to: Vitocal 100-AW AM2V outdoor unit
Likely causes
- Insufficient water flow
- Improper selection
- Terminal not opened
Test and repair steps
- Check that the water pump runs and that its indicator light shows no fault.
- Open the high point exhaust valve and check for intermittent gas discharge.
- Check the water circuit length and elbows, and calculate water resistance.
- Confirm all water system valves that should be open are open.
- Clean the water circuit filter.
- Replace the pump or add a secondary pump if the water resistance is too high.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
- E20 Exhaust temperature overprotection
- E23 Fan 1 overload speed limit
- E24 Fan 2 overload speed limit
- E25 Inlet/outlet water temperature difference exceeded
- E27 Mixing outlet water temperature sensor failure
- E28 Hot water return temp sensor failure
- E29 Hot water outlet water temp sensor failure
- E34 High pressure protection, 3 times
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal 100-AW AM2V installation, service and operating instructions, p. 75. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.