Rinnai · Tankless water heater
Perf data Performance data viewer (live readings and counters)
What the display is showing
Read-only menu on the temperature controller that shows live readings and lifetime counters as numbered items. Nothing is wrong when you use it. Several item numbers are the same as fault code numbers (02, 03, 05, 07, 10, 11, 12, 15, 17, 19, 21, 22, 30, 31), so a number is a reading only while you are inside this menu. Which items exist depends on the model: the installation manuals list items 01 to 21, the troubleshooting guide also lists 22 to 31 and A0 to C2 for RX/CX and CX units; the tech sheet inside the front cover has the final list for the model.
Applies to: Rinnai tankless water heaters, non-SENSEI, SENSEI and SENSEI RX/CX
What to do
- Press and hold Down; after 2 seconds also press and hold On/Off (both together).
- (RX/CX) wait until 01 appears.
- Use Up and Down to scroll through the item numbers.
- To exit, repeat the Down + On/Off press. The set temperature comes back on the display.
- Items 01 water flow (x0.1 gal/min)
- 02 outgoing water temperature (°F)
- 03 combustion hours (x100 h)
- 04 combustion cycles (counts over 999 are shown in two parts, low and high, see Table 1 in the guide)
- 05 fan frequency (Hz)
- 06 extra controllers present (1 = yes, 2 = no)
- 07 flow control valve position (0 = mid, 1 = open, 2 = closed)
- 08 inlet water temperature (°F)
- 09 fan current (x10 mA)
- 10 total bath fill amount (gal)
- 11 heat exchanger outlet temperature (°F)
- 12 bypass flow control position (degrees open)
- 15 freeze protection temperature, indoor units (°F)
- 17 freeze protection temperature, outdoor units and RX/CX (°F)
- 19 pump hours (x100 h)
- 20 pump cycles
- 21 exhaust temperature (°F)
- 22 pump frequency, RX/CX (Hz)
- 23 lime detecting temperature, RX/CX (°F)
- 24 descaling cycles, RX/CX
- 30 upper tank thermistor, CX (°F)
- 31 lower tank thermistor, CX (°F)
- A0, A1, A2 total hot water delivered first 3 digits (gal), middle 3 digits (x1,000 gal), top 3 digits (x1,000,000 gal)
- C0, C1, C2 total gas input first 3 digits (x100 kcal), middle (x100,000 kcal), top (x100,000,000 kcal)
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
96 models in Non-SENSEI, SENSEI RX/CX, SENSEI
Other codes on the same units
- Mute Controller key beeps on/off
- Out Initial setting: outdoor installation
- Parameter mode Parameter settings menu
- Parameter settings Parameter (installer settings) mode
- Performance data Performance data readout mode
- Priority light Priority light on (this controller is in charge)
- S Venturi reset sequence: step S (SENSEI)
- SE Cascade diagnostic display (error on secondary unit)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), View Performance Data p.73-75; Rinnai N-Series Residential (100000467) / with Pump (100000508) / Commercial (100000504) / RSC SENSEI (100000773) Installation and Operation Manuals, 5.5 Performance Data; Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 5.5 p.58. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.