Rinnai · Tankless water heater
SE Cascade diagnostic display (error on secondary unit)
What the control is telling you
In a cascade of commercial units, the primary heater's display alternates between SE and the set temperature whenever any secondary heater is showing an error code.
Applies to: SENSEI Commercial and SENSEI CX Series (cascade installations)
Likely causes
- An error code is active on a secondary water heater in the cascade
- Primary unit relaying a fault from a cascaded secondary unit
Test and repair steps
- Note that SE appears only on SENSEI Commercial and SENSEI CX Series units connected in cascade.
- When the primary unit flashes SE and the set temperature, check the secondary heaters to find which one is displaying an error code, then troubleshoot that code.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
30 models in SENSEI, SENSEI RX/CX
Other codes on the same units
- Perf data Performance data viewer (live readings and counters)
- Performance data Performance data readout mode
- Priority light Priority light on (this controller is in charge)
- S Venturi reset sequence: step S (SENSEI)
- SEt Initial settings not yet confirmed
- SS Service Soon alert (also listed as 55)
- SS (55) Code SS (55)
- Water flow fault (no code displayed) No-code water flow fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.65. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.