Rinnai · Tankless water heater
Priority light Priority light on (this controller is in charge)
What the display is showing
The orange Priority light glows on the controller that currently sets the temperature; the water heater is then ready to supply hot water. If it is off, press Priority on that controller. Priority can be moved only when no tap is open. On RX/CX units the Priority LED blinks during first power-up while SEt is displayed.
Applies to: Rinnai SENSEI, SENSEI RX/CX and KCM tankless with temperature controllers
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
30 models in SENSEI RX/CX, SENSEI, KCM (RUCS/RUS)
Other codes on the same units
- Parameter mode Parameter settings menu
- Parameter settings Parameter (installer settings) mode
- Perf data Performance data viewer (live readings and counters)
- Performance data Performance data readout mode
- S Venturi reset sequence: step S (SENSEI)
- SE Cascade diagnostic display (error on secondary unit)
- SEt Initial settings not yet confirmed
- SS Service Soon alert (also listed as 55)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai N-Series Residential (100000467) / with Pump (100000508) / Commercial (100000504) / RSC SENSEI (100000773) Installation and Operation Manuals, 5.4 Setting the Temperature p.70; Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 5.4 p.57; Rinnai KCM Series Manual (U328-0700X04), p.54. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.