Rinnai · Tankless water heater

Parameter mode Parameter settings menu

Menu / mode display SENSEI RX/CXSENSEI

What the display is showing

Installer menu used to change the heater's parameter settings with the A and B pushbuttons on the PC board together with the controller keys. The controller shows the setting number with its choice letter, for example 01A changing to 01b. Do not change parameters unless an instruction calls for it. On RX/CX the gas-type parameter (10) can only be changed within 20 minutes after power is supplied.

Applies to: Rinnai SENSEI tankless (RU, RUR, RSC, CU) and SENSEI RX/CX (RX, RXP, CX, CXP)

What to do

  1. Open the unit and locate pushbuttons A and B on the PC board.
  2. Press A for 1 second the controller shows a setting such as 01A.
  3. Use Up and Down on the controller to choose the setting number.
  4. Press On/Off on the controller to change the choice letter (for example 01A to 01b).
  5. Press A for 1 second to leave the menu and save.

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

30 models in SENSEI RX/CX, SENSEI

CU160eCU160iCU199eCU199iCX160iCX199iCXP160iCXP199iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRUR160eRUR160iRUR199eRUR199iRX130iRX160iRX180iRX199iRXP160iRXP199i

Other codes on the same units

  • Lock key Controller locked (key symbol)
  • Mute Controller key beeps on/off
  • Out Initial setting: outdoor installation
  • Parameter settings Parameter (installer settings) mode
  • Perf data Performance data viewer (live readings and counters)
  • Performance data Performance data readout mode
  • Priority light Priority light on (this controller is in charge)
  • S Venturi reset sequence: step S (SENSEI)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai N-Series Residential (100000467) / with Pump (100000508) / Commercial (100000504) / RSC SENSEI (100000773) Installation and Operation Manuals, 4.12 Configure Parameter Settings p.61; Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 4.13 p.48. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.