Rinnai · Tankless water heater

S Venturi reset sequence: step S (SENSEI)

Menu / mode display SENSEI

What the display is showing

A screen shown on SENSEI (non RX/CX) units while stepping through the venturi/gas valve reset procedure by pressing button B on the PC board for 1 second at a time. It comes after F and before E.

Applies to: Rinnai SENSEI tankless (RU, RUR, RSC, CU)

What to do

  1. Press B for 1 second from the F screen to reach S, then press B again for E.

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

20 models in SENSEI

CU160eCU160iCU199eCU199iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRUR160eRUR160iRUR199eRUR199i

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), Code 17 and Code 52 reset procedure p.28-29. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.