Noritz · Tankless water heater

63 Recirculation abnormality (no recirculation flow)

Medium severity Noritz NRCR

What the control is telling you

NRCR only. The unit is running the built-in recirculation pump but sees no recirculation flow.

Applies to: Noritz NRCR92 / NRCR111

Likely causes

  • Clogged return line filter or closed shut-off valves
  • Air in the hot and return lines (dedicated return mode)
  • 'Crossover' connector not plugged together, crossover valve filter clogged or valve installed backwards (crossover mode)
  • Failed recirculation pump, recirculation flow sensor or circuit board (older installs)

Test and repair steps

  1. Check that the return line and water shut-off valves are open and clean the return line filter.
  2. Dedicated return purge air from the domestic hot and return lines.
  3. In crossover mode, make sure the 'Crossover' connector is plugged in, clean the filter on the crossover valve, and confirm the valve faces the right way.
  4. Check MM86 to confirm which recirculation mode the unit is set to and MM17 for recirculation flow.
  5. Use Trial Operation for the pump in the EZ Start Plus app.
  6. Older installs check the recirculation pump, recirculation flow sensor and circuit board.

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

2 models in Noritz NRCR

NRCR111DVNRCR92DV

Other codes on the same units

  • 16 Abnormally high outlet temperature
  • 20 High limit switch tripped
  • 061 Recirculation abnormality (sub-code of 06)
  • 062 Recirculation abnormality (sub-code of 06)
  • 65 Main water control servo abnormality
  • 66 Bypass water control servo abnormality
  • 73 Circuit board setting abnormality
  • 90 Combustion abnormality

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR/CDV Level 2 Maintenance & Troubleshooting (Premix R2 V2), 63 error code, p.14; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), NRCR Pro specific error codes, p.29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.