Noritz · Tankless water heater
73 Circuit board setting abnormality
What the control is telling you
DIP switches or connectors were changed while the unit had power. On premix units it also shows when a replacement board was installed but not programmed.
Applies to: All Noritz residential tankless (EZ, NRCR, NCC199CDV, NRC/NRCP)
Likely causes
- DIP switches or connectors changed with power on
- Replacement circuit board not programmed (premix)
Test and repair steps
- Unplug the unit.
- Finish all DIP switch and wiring changes with the power off.
- Plug the heater back in and check that the code clears.
- Premix with new board program the board (EZ Start Plus app or built-in display) for model, gas type and venting.
Settings for these units
- Indoor clearances (required and recommended) · Noritz NRCR
- Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR
- Water quality limits · Noritz EZ, Noritz NRCR
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Noritz EZ/NRCR/CDV Level 2 Maintenance & Troubleshooting (Premix R2 V2), 73 & F76 error codes, p.15; Noritz Residential Level 2 Maintenance & Troubleshooting (NRC/NRCP and older, R2 V1), 73 & F76 error codes, p.9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.