Noritz · Tankless water heater

902 Combustion abnormality (sub-code of 90)

High severity Noritz EZNoritz NRCR

What the control is telling you

EZ/NRCR owner's guide lists 901 and 902 with 90: air supply or exhaust may be blocked, low gas pressure, or condensate drain clogged.

Applies to: Noritz EZ111/EZ98/EZ71 and NRCR111/NRCR92

Likely causes

  • Clogged air supply (indoor air) or exhaust
  • Low gas supply pressure
  • Clogged or frozen condensate drain line

Test and repair steps

  1. Check the air supply opening and exhaust vent for blockage.
  2. Check inlet gas pressure (NG 3.5-10.5 in. WC, LP 8-14 in. WC).
  3. Check the condensate line for clogs or ice.
  4. Follow the code 90 steps for MM31/MM32 checks and fan/venturi cleaning.

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

5 models in Noritz EZ, Noritz NRCR

EZ111DVEZ71DVEZ98DVNRCR111DVNRCR92DV

Other codes on the same units

  • 73 Circuit board setting abnormality
  • 90 Combustion abnormality
  • 91 Gas conversion not done correctly
  • 901 Combustion abnormality (sub-code of 90)
  • C1# Descaling reminder (C11-C19)
  • F76 Multi-system communication error
  • MM14 Maintenance monitor 14 - flow rate
  • MM30 Maintenance monitor 30 - inlet water temperature

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.