Noritz · Tankless water heater
MM30 Maintenance monitor 30 - inlet water temperature
What the display is showing
Shows incoming cold water temperature. Use with flow and set temperature to work out temperature rise and gas demand (BTU = gpm x temperature rise x 500).
Applies to: EZ, NRCR, CDV, NRC/NRCP
What to do
- Open the maintenance monitor (display window, remote or EZ Start Plus app).
- Select the MM number.
- Read the value, compare with set temperature and expected behaviour.
Settings for these units
Indoor clearances (required and recommended) · Noritz NRCR
| Location | Required | Recommended (service) |
|---|---|---|
| Top | 12 in. (300 mm) | 3 in. (76 mm) above and below exhaust |
| Front | 4 in. (100 mm) | 24 in. (610 mm) |
| Sides | 3 in. (76 mm) | 8 in. (203 mm) |
Required clearances apply to both combustible and non-combustible materials.
Recommended space is for service and quick access to gas and water shut-offs.
Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR
| Setting | Options | Default |
|---|---|---|
| Max Set Temperature (power off) | 100-140 F in 5 F steps; 37-48 C, 50-60 C | 120 F / 50 C |
| Recirc ON/OFF | ON / OFF | OFF |
| Recirc Mode | Always OFF, Always ON, Manual Timer, Auto Learning (NRCR) | Always OFF |
| Vacation Mode | Active / Inactive | Inactive |
| Flow Meter Alarm | 10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFF | Alarm OFF |
| Drain Water (power off) | Start / Cancel | Cancel |
| Scale Flushing (power off) | Start / Cancel | Cancel |
| Audible Alarm | ON / OFF | ON |
| Screen Lock | Active / Inactive (4-digit password) | Inactive |
| Units (first 10 min after power-up, power off) | [F/gal/ft] or [C/L/m] | [F/gal/ft] |
| Power Saving Dis. / Backlight | ON-OFF / Power Save ON-OFF | ON / Power Save ON |
| Brightness / Contrast / Touch Sound | Bright-Normal-Dim-Dark / -15 to +15 / ON-OFF | Normal / Standard / ON |
Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.
Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).
- Water quality limits · Noritz EZ, Noritz NRCR
Models that show this code
12 models in Noritz EZ, Noritz NRCR, Noritz CDV, Noritz NRC/NRCP
Other codes on the same units
- 902 Combustion abnormality (sub-code of 90)
- C1# Descaling reminder (C11-C19)
- F76 Multi-system communication error
- MM14 Maintenance monitor 14 - flow rate
- MM31 Maintenance monitor 31 - outlet water temperature
- MM32 Maintenance monitor 32 - heat exchanger water temperature
- MM49 Maintenance monitor 49 - fan speed
- MM86 Maintenance monitor 86 - recirculation mode
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Noritz EZ/NRCR/CDV Level 2 (Premix R2 V2), Maintenance Monitors, p.18-21; Noritz Residential Level 2 (NRC/NRCP and older, R2 V1), Maintenance Monitors, p.12-14. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.