Noritz · Tankless water heater

90 Combustion abnormality

High severity Noritz EZNoritz NRCRNoritz CDVNoritz NRC/NRCP

What the control is telling you

On EZ/NRCR/CDV (premix): the unit cannot reach set temperature, most often from restricted intake/exhaust, wrong DIP/vent settings, a clogged condensate drain, low gas pressure, or on older units a dirty fan/venturi. On NRC/NRCP (non-premix): two main causes, not reaching set temperature and/or the fan speed over-correcting (MM49 above 100) because of air restriction. Owner's guide shows 901 and 902 with the same meaning.

Applies to: All Noritz residential tankless (EZ, NRCR, NCC199CDV, NRC/NRCP)

Likely causes

  • Blocked or restricted intake or exhaust (lint, debris, animals, bad termination)
  • Wrong DIP switch / vent settings
  • Clogged or frozen condensate drain line (premix)
  • Insufficient inlet gas pressure
  • Dirty fan or venturi (older installs)
  • Bypass servo stuck (outlet temp low but HEX temp high)

Test and repair steps

  1. Check the intake and exhaust terminations, screens, and any blockage (lint, nests, animals); fix wrong or restricted venting.
  2. Indoor air supply look for lint, dust or oil (laundry rooms) at the air supply; clean the intake filter.
  3. Measure inlet gas pressure under full demand. Premix (EZ, NRCR, NCC199CDV) inlet gas: NG 3.5-10.5 in. WC, LP 8-14 in. WC. NRC/NRCP inlet gas: up to 199k Btu/h NG 4-10.5 in. WC, LP 8-14 in. WC; over 199k Btu/h NG 5-10.5 in. WC, LP 10.5-14 in. WC.
  4. Premix (EZ/NRCR/CDV) check the condensate drain is not clogged or frozen.
  5. Premix verify vent type/length and other settings with the PROCard app (DIP switches) or EZ Start Plus app / display (Pro models).
  6. Read MM31 (outlet) and MM32 (heat exchanger): MM32 high but MM31 low = bypass servo problem; both low = burner not heating enough, usually not enough gas.
  7. NRC/NRCP read MM49 fan speed with the front cover ON; normal is 100, above 100 means intake or exhaust restriction.
  8. Older installs clean the fan (air compressor, vacuum or plastic brush) and venturi; vacuum the burner, never blow it out (see guide 'Cleaning the fan and burner - Noritz EZ/NRCR/CDV').

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

12 models in Noritz EZ, Noritz NRCR, Noritz CDV, Noritz NRC/NRCP

EZ111DVEZ71DVEZ98DVN-0841MCN-0841MC-DVN-0842MCN-0842MC-DVNCC199CDVNRC111-DVNRC111-SVNRCR111DVNRCR92DV

Other codes on the same units

  • 63 Recirculation abnormality (no recirculation flow)
  • 65 Main water control servo abnormality
  • 66 Bypass water control servo abnormality
  • 73 Circuit board setting abnormality
  • 91 Gas conversion not done correctly
  • 901 Combustion abnormality (sub-code of 90)
  • 902 Combustion abnormality (sub-code of 90)
  • C1# Descaling reminder (C11-C19)

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR/CDV Level 2 Maintenance & Troubleshooting (Premix R2 V2), 90 error code and MM31/MM32, p.16-17, 20-21; Noritz Residential Level 2 Maintenance & Troubleshooting (NRC/NRCP and older, R2 V1), 90 error code and MM49, p.10-11, 15; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), Gas line conditions, p.20; Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.