061 Recirculation abnormality (sub-code of 06)

Low severity Noritz NRCR

What the control is telling you

NRCR only. Listed with 06 in the owner's guide as recirculation abnormality.

Applies to: Noritz NRCR92 / NRCR111

Likely causes

  • Clogged return line filter
  • Clogged crossover valve filter
  • Air in the return line

Test and repair steps

  1. Clean the return line filter.
  2. Clean the crossover valve filter and check its orientation.
  3. Purge air from the hot and return lines (dedicated mode).
  4. Follow code 06 / 63 steps if it returns.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.