16 Abnormally high outlet temperature

High severity Noritz EZNoritz NRCRNoritz CDVNoritz NRC/NRCP

What the control is telling you

The outlet water got hotter than allowed. Same meaning on all families. Most common cause is scale in the heat exchanger and water parts; wrong gas type is also listed for premix units.

Applies to: All Noritz residential tankless (EZ, NRCR, NCC199CDV, NRC/NRCP)

Likely causes

  • Hard water scale built up in the heat exchanger, water control parts, or both
  • Wrong gas type (premix units)
  • Clogged inlet filter screen reducing flow

Test and repair steps

  1. Check water hardness; Noritz requires treatment above 12 gpg (200 mg/L).
  2. Descale the heat exchanger with the descale kit (1 hour, 50/50 mix of water and calcium/lime/rust remover).
  3. Clean the cold water inlet filter (and recirculation filter on NRCR).
  4. Premix confirm the gas type setting matches the gas supplied and that LP conversion was done correctly (sticker on unit).
  5. Use MM31 (outlet) and MM32 (heat exchanger) temperature to confirm readings during a draw.
  6. Advise a water softener or scale inhibitor to prevent repeat scale.

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

12 models in Noritz EZ, Noritz NRCR, Noritz CDV, Noritz NRC/NRCP

EZ111DVEZ71DVEZ98DVN-0841MCN-0841MC-DVN-0842MCN-0842MC-DVNCC199CDVNRC111-DVNRC111-SVNRCR111DVNRCR92DV

Other codes on the same units

  • 10 Abnormal combustion (NRCR, gas supply related)
  • 11 Ignition failure (no flame detected)
  • 12 Flame loss (repeated)
  • 14 Thermal fuse failure
  • 20 High limit switch tripped
  • 29 Condensate collector water level abnormal
  • 061 Recirculation abnormality (sub-code of 06)
  • 062 Recirculation abnormality (sub-code of 06)

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR/CDV Level 2 Maintenance & Troubleshooting (Premix R2 V2), 16 & 20 error codes, p.14; Noritz Residential Level 2 Maintenance & Troubleshooting (NRC/NRCP and older, R2 V1), Descaling/flushing and 14, 16, 20 error codes, p.3, 8; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), Poor water quality issues, p.32. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.