KeepRite · Furnace

LED steady ON Status LED on solid - control lockout (resets after 1 hour)

High severity KeepRite (F/G)9MXE Single-Stage FurnaceKeepRite (F/G)9MXT Two-Stage Furnace

What the control is telling you

A steady green light (no heartbeat, no flashing) means the board has locked itself out. It clears on its own after 1 hour.

Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces

Likely causes

  • Fault in the flame sensing circuit
  • Gas valve relay stuck closed on the board
  • Internal software check failure

Test and repair steps

  1. Cycle power to the furnace to clear the lockout.
  2. Watch a full heating cycle.
  3. If the steady light comes back, replace the furnace control.

Settings for these units

Models that show this code

16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace

G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422AG9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 7 Limit circuit lockout
  • 8 Gas heating lockout - manual reset needed
  • 9 High-heat pressure switch or relay did not close or reopened
  • 10 Line voltage polarity reversed
  • Component self-test Run all furnace components for a short test
  • LED heartbeat Control OK - idle or running, no faults
  • LED off Status LED dark - no power to the control or blown 3 A fuse
  • Stored fault recall Read the last stored fault code from the control

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.