KeepRite · Furnace

10 Line voltage polarity reversed

Medium severity KeepRite (F/G)9MXE Single-Stage FurnaceKeepRite (F/G)9MXT Two-Stage FurnaceKeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace

What the control is telling you

The control sees 115 V polarity reversed (or the furnace is not grounded) and will not heat. On 96VTN the light flashes rapidly.

Applies to: KeepRite (F/G)9MXE, (F/G)9MXT and (F/G)96VTN furnaces

Likely causes

  • Hot and neutral swapped
  • Poor or missing ground
  • Twinned units with 24 V transformers out of phase

Test and repair steps

  1. Turn power off and correct the hot/neutral connections to the furnace.
  2. Confirm a solid ground to the furnace and control.
  3. On twinned furnaces, check the 24 V transformer phasing.

Settings for these units

Filter size by casing width · KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace

Casing width (in.)Side return filterBottom return filterType
14-3/1616 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
17-1/216 x 25 x 3/4 in.16 x 25 x 3/4 in.Washable
2116 x 25 x 3/4 in.20 x 25 x 3/4 in.Washable
24-1/216 x 25 x 3/4 in.24 x 25 x 3/4 in.Washable

Aim for filter pressure drop under 0.2 in. w.c. (best under 0.1).

Never run without a filter.

Models that show this code

25 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace, KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace

G96VTN0401410G96VTN0401712G96VTN0601412G96VTN0601714G96VTN0801716G96VTN0802120G96VTN1002120G96VTN1002122G96VTN1202422G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422AG9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 6+1 Ignition lockout after 4 failed tries
  • 7 Limit circuit lockout
  • 8 Gas heating lockout - manual reset needed
  • 9 High-heat pressure switch or relay did not close or reopened
  • Component self-test Run all furnace components for a short test
  • LED heartbeat Control OK - idle or running, no faults
  • LED off Status LED dark - no power to the control or blown 3 A fuse
  • LED steady ON Status LED on solid - control lockout (resets after 1 hour)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25; KeepRite_ICP_F_G_96VTN_KeepRite_G96VTN_Tempstar_Heil_Arcoaire_installation_440_01_4801_00.txt - section Start-up, Adjustment and Safety Check / 115-V Wiring. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.