KeepRite · Furnace

Component self-test Run all furnace components for a short test

Menu / mode display KeepRite (F/G)9MXE Single-Stage FurnaceKeepRite (F/G)9MXT Two-Stage Furnace

What the display is showing

Runs the inducer, igniter and blower speeds for a short time so you can see each part work. The gas valve and the humidifier terminal are not energized. It will not start with any thermostat signal present or while time delays are running. Holding the jumper longer than 2 seconds makes the LED flash code 10 and the request is ignored.

Applies to: (F/G)9MXE and (F/G)9MXT furnaces

What to do

  1. Remove the blower door, disconnect the thermostat R lead at the control and hold the blower door switch closed.
  2. Jumper terminal C to the TEST/TWIN quick-connect for about 2 seconds, until the LED goes off, then remove the jumper.
  3. The LED repeats the previous status code 4 times, then the inducer starts.
  4. 9MXT igniter on after 7 s for 15 s; blower runs LO-HT, HI-HT, COOL speed 10 s each; inducer drops to low for 10 s and stops.
  5. 9MXE igniter on after 7 s for 15 s; blower runs continuous-fan, heat and cool speed 10 s each; inducer stops.
  6. Reconnect R, restore the door, then confirm the furnace shuts down and restarts from the thermostat.

Settings for these units

Models that show this code

16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace

G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422AG9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 7 Limit circuit lockout
  • 8 Gas heating lockout - manual reset needed
  • 9 High-heat pressure switch or relay did not close or reopened
  • 10 Line voltage polarity reversed
  • LED heartbeat Control OK - idle or running, no faults
  • LED off Status LED dark - no power to the control or blown 3 A fuse
  • LED steady ON Status LED on solid - control lockout (resets after 1 hour)
  • Stored fault recall Read the last stored fault code from the control

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Component Self-Test, p.14-15; (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, p.14-15. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.