KeepRite · Furnace
7 Limit circuit lockout
What the control is telling you
The limit or rollout switch stayed open more than 3 minutes. The control auto-resets after 3 hours.
Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces
Likely causes
- Same causes as code 4 (airflow, overfire, faulty limit)
Test and repair steps
- Follow the code 4 checks.
- Reset the rollout switch only after the cause is fixed.
- Cycle power to clear the lockout and run a full heat cycle while checking temperature rise.
Settings for these units
- Filter size by casing width · KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace
Models that show this code
16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace
Other codes on the same units
- 4 Limit or rollout circuit open
- 5 Flame sensed with gas valve off
- 6 Flame not proved during ignition trial
- 6+1 Ignition lockout after 4 failed tries
- 8 Gas heating lockout - manual reset needed
- 9 High-heat pressure switch or relay did not close or reopened
- 10 Line voltage polarity reversed
- Component self-test Run all furnace components for a short test
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.