KeepRite · Furnace

8 Gas heating lockout - manual reset needed

Critical severity KeepRite (F/G)9MXE Single-Stage FurnaceKeepRite (F/G)9MXT Two-Stage Furnace

What the control is telling you

The control has locked out gas heat and will NOT reset itself. Turn power off for 5 minutes, then retry.

Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces

Likely causes

  • Gas valve relay on the board stuck closed
  • Gas valve wire miswired or shorted

Test and repair steps

  1. Warning: this lockout points to a valve circuit fault - check carefully before restoring gas.
  2. Turn power off, wait 5 minutes, power back on.
  3. Inspect the gas valve wiring for miswiring or a short.
  4. If the code returns with good wiring, replace the furnace control.

Settings for these units

Models that show this code

16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace

G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422AG9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 5 Flame sensed with gas valve off
  • 6 Flame not proved during ignition trial
  • 6+1 Ignition lockout after 4 failed tries
  • 7 Limit circuit lockout
  • 9 High-heat pressure switch or relay did not close or reopened
  • 10 Line voltage polarity reversed
  • Component self-test Run all furnace components for a short test
  • LED heartbeat Control OK - idle or running, no faults

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.