KeepRite · Furnace

9 High-heat pressure switch or relay did not close or reopened

High severity KeepRite (F/G)9MXT Two-Stage Furnace

What the control is telling you

Two-stage models: the high-heat pressure switch (or the relay that drives high heat) did not close, or opened again.

Applies to: KeepRite (F/G)9MXT two-stage 95% furnace

Likely causes

  • Faulty control relay
  • Gas valve miswired
  • Any of the venting/drain/pressure switch causes listed for code 3

Test and repair steps

  1. Check the gas valve wiring against the diagram.
  2. Go through the code 3 checks for vent, drain, tubing and inducer.
  3. Check the high-heat switch with a manometer during high-fire.
  4. If wiring and switch are fine, the board relay is suspect - replace the control.

Settings for these units

Models that show this code

8 models in KeepRite (F/G)9MXT Two-Stage Furnace

G9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 6 Flame not proved during ignition trial
  • 6+1 Ignition lockout after 4 failed tries
  • 7 Limit circuit lockout
  • 8 Gas heating lockout - manual reset needed
  • 10 Line voltage polarity reversed
  • Component self-test Run all furnace components for a short test
  • LED heartbeat Control OK - idle or running, no faults
  • LED off Status LED dark - no power to the control or blown 3 A fuse

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.