KeepRite · Furnace
LED off Status LED dark - no power to the control or blown 3 A fuse
What the control is telling you
The green status light shows nothing at all, so the board is not getting 115 V or 24 V.
Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces
Likely causes
- Breaker off or open wiring from the panel
- Blower door switch open or failed
- Transformer not putting out 24 V
- 3 A board fuse blown by a short in the 24 V wiring
- Failed furnace control
Test and repair steps
- Confirm 115 V between L1 and neutral at the control; if missing, check the door switch and the breaker/wiring back to the panel.
- With 115 V present, measure 24 V between the 24VAC and COM terminals.
- If 24 V is missing and the fuse is fine, the transformer is bad - replace it.
- If the 3 A fuse is open, look for a shorted low-voltage wire (thermostat cable included) before fitting a new 3 A fuse only.
- If power and fuse are both good and the light is still dark, change the control board.
Settings for these units
- Filter size by casing width · KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace
Models that show this code
16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace
Other codes on the same units
- 7 Limit circuit lockout
- 8 Gas heating lockout - manual reset needed
- 9 High-heat pressure switch or relay did not close or reopened
- 10 Line voltage polarity reversed
- Component self-test Run all furnace components for a short test
- LED heartbeat Control OK - idle or running, no faults
- LED steady ON Status LED on solid - control lockout (resets after 1 hour)
- Stored fault recall Read the last stored fault code from the control
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.