23 Combination error

Medium severity Fujitsu ductless split/multi/VRF (general code list)Fujitsu wall-mounted 7-15 (NA ASU/AOU type)Fujitsu slim duct ARU 7-18 (LL type)

What the control is telling you

Outdoor unit received refrigerant / model information from an indoor unit that is not an allowed match. Indoor lamps: OPERATION (green) flashes 2x, TIMER (orange) flashes 3x, ECONOMY (green) flashes fast nonstop; wired remote shows 23.

Applies to: Fujitsu ductless heat pumps: Fujitsu ductless split/multi/VRF (general code list), Fujitsu wall-mounted 7-15 (NA ASU/AOU type), Fujitsu slim duct ARU 7-18 (LL type)

Likely causes

  • Incompatible indoor unit connected

Test and repair steps

  1. Check the model of each connected indoor unit against the outdoor unit's approved list.
  2. If correct, replace the outdoor main PCB.

Settings for these units

Other codes on the same units

  • 15 Check run unfinished / airflow auto-adjust error
  • 16 Peripheral unit / transmission PCB connection error
  • 21 Address / refrigerant circuit setting error
  • 22 Indoor unit capacity error
  • 24 Connection unit number error
  • 26 Indoor unit address setting error
  • 27 Primary / secondary unit setup error
  • 29 Connection unit number error (wired remote system)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu All Fujitsu split - multi - VRF (generic code list) codes.pdf - section error code table (indoor LED flashes); Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 14 Error codes; Fujitsu Wall-mounted KMCG (ASEH-AOEH 07-14) - Fujitsu UK; same error-code scheme as NA ASU-AOU units service S.pdf - section 3 Troubleshooting, 2 Troubleshooting with error code; Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.