Fujitsu · Heat pump

16 Peripheral unit / transmission PCB connection error

Medium severity Fujitsu ductless split/multi/VRF (general code list)Fujitsu slim duct ARU 7-18 (LL type)

What the control is telling you

A peripheral or transmission PCB (option kit) is not connecting to the indoor board. Indoor lamps: OPERATION (green) flashes 1x, TIMER (orange) flashes 6x, ECONOMY (green) flashes fast nonstop; wired remote shows 16.

Applies to: Fujitsu ductless heat pumps: Fujitsu ductless split/multi/VRF (general code list), Fujitsu slim duct ARU 7-18 (LL type)

Likely causes

  • Option PCB plug loose
  • Option kit fault
  • Indoor PCB fault

Test and repair steps

  1. Check option kit cables at the indoor board (e.g. CN65 / CN47).
  2. Remove and refit the kit; replace it if the error stays.
  3. Replace the indoor main PCB as a last step.

Settings for these units

Other codes on the same units

  • 11 Serial communication error (indoor/outdoor)
  • 12 Wired remote controller communication error
  • 14 Network communication error
  • 15 Check run unfinished / airflow auto-adjust error
  • 21 Address / refrigerant circuit setting error
  • 22 Indoor unit capacity error
  • 23 Combination error
  • 24 Connection unit number error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu All Fujitsu split - multi - VRF (generic code list) codes.pdf - section error code table (indoor LED flashes); Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.