Fujitsu · Heat pump
22 Indoor unit capacity error
What the control is telling you
Connected indoor capacity does not suit the outdoor unit (checked in the first 3 min after power-up). Indoor lamps: OPERATION (green) flashes 2x, TIMER (orange) flashes 2x, ECONOMY (green) flashes fast nonstop; wired remote shows 22.
Applies to: Fujitsu ductless heat pumps: Fujitsu ductless split/multi/VRF (general code list), Fujitsu wall-mounted 7-15 (NA ASU/AOU type), Fujitsu slim duct ARU 7-18 (LL type)
Likely causes
- Wrong indoor sizes for this outdoor / multi combination
- Main PCB fault
Test and repair steps
- Add up the indoor capacities and compare with the allowed range and combination table of the outdoor unit.
- Correct the selection.
- If the combination is right, replace the main PCB.
Settings for these units
- Operating range and service space · Fujitsu multi-zone outdoor 18/24 type
Other codes on the same units
- 14 Network communication error
- 15 Check run unfinished / airflow auto-adjust error
- 16 Peripheral unit / transmission PCB connection error
- 21 Address / refrigerant circuit setting error
- 23 Combination error
- 24 Connection unit number error
- 26 Indoor unit address setting error
- 27 Primary / secondary unit setup error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Fujitsu All Fujitsu split - multi - VRF (generic code list) codes.pdf - section error code table (indoor LED flashes); Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 14 Error codes; Fujitsu Wall-mounted KMCG (ASEH-AOEH 07-14) - Fujitsu UK; same error-code scheme as NA ASU-AOU units service S.pdf - section 3 Troubleshooting, 2 Troubleshooting with error code; Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.