Carrier · Heat pump

PC 02 Compressor top or IPM temperature protection

High severity D5FUHA

What the control is telling you

Some models have overload protection. The code shows if the sampling voltage is not 5 V or if the IPM module temperature is above a set value. Prepare connection wires, outdoor PCB, IPM module board, high pressure protector, and check for system blockages.

Applies to: D5FUHA heat pump outdoor unit

Likely causes

  • Blocked indoor or outdoor airflow
  • High compressor top temperature
  • Refrigerant system fault or blockage
  • Loose OLP sensor connection or faulty OLP
  • Loose PCB or IPM radiator screws

Test and repair steps

  1. Check that the indoor and outdoor airflow is not blocked. Clear the air inlets, outlets, and heat exchangers.
  2. Turn the power off and back on after 10 minutes.
  3. Check the compressor top temperature. If it is above 90°C, check the refrigerant system and repair it if needed.
  4. Check the OLP connection. Correct any loose connection.
  5. Measure the resistance between the two OLP ports. It should be zero. If not, replace the OLP.
  6. Check the fastening screws on the PCB and IPM radiator. Tighten them and apply silicone grease if needed.
  7. If the fault remains, replace the outdoor control PCB.

Other codes on the same units

  • FHCC Refrigerant sensor error
  • PC 00 Outdoor IPM module protection
  • PC 01 Outdoor voltage protection
  • PC 03 High or low pressure protection
  • PC 04 Inverter compressor drive error
  • PC 06 Quick maintenance code (outdoor)
  • PC 08 Quick maintenance code (outdoor)
  • PC 0F Quick maintenance code (outdoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FUHA Service Manual, p. 35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.