Carrier · Heat pump

FHCC Refrigerant sensor error

High severity D5FUHA

What the control is telling you

Refrigerant sensor fault.

Applies to: D5FUHA indoor unit

Other codes on the same units

  • EHbA Communication error between indoor unit and external fan module
  • FC Forced cooling mode
  • PC 00 Outdoor IPM module protection
  • PC 01 Outdoor voltage protection
  • PC 02 Compressor top or IPM temperature protection
  • PC 03 High or low pressure protection
  • PC 04 Inverter compressor drive error
  • PC 06 Quick maintenance code (outdoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FUHA service manual, p. 20. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.