PC 01 Outdoor voltage protection
What the control is telling you
Abnormal rises or drops in voltage are detected by the voltage detection circuit. Recommended parts: power supply wires, IPM module board, PCB, reactor.
Applies to: D5FUHA
Likely causes
- Incorrect or unstable supply voltage
- Faulty power supply wires or connections
- Faulty IPM board
- Faulty reactor
- Faulty outdoor PCB
Test and repair steps
- Check the power supply. If it is not in working order, turn off the unit.
- Check the connections and wires. Ensure proper connections or replace the wires.
- Power on and measure the voltage between P and N.
- While in standby, check whether the voltage between P and N is about DC 310 V, 340 V or 380 V. At start-up, check it is in the 220 V to 400 V range.
- If the voltage is wrong, replace the IPM board.
- Check the reactor. If it is not working, replace the reactor.
- If the reactor is good, replace the outdoor PCB.
- On models where the electric control box cover cannot be removed, skip the check steps as directed in the disassembly guide.
Other codes on the same units
- FHCC Refrigerant sensor error
- PC 00 Outdoor IPM module protection
- PC 02 Compressor top or IPM temperature protection
- PC 03 High or low pressure protection
- PC 04 Inverter compressor drive error
- PC 06 Quick maintenance code (outdoor)
- PC 08 Quick maintenance code (outdoor)
- PC 0F Quick maintenance code (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUHA service manual, p. 31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.