Carrier · Heat pump
PC 04 Inverter compressor drive error
What the control is telling you
An abnormal inverter compressor drive is detected by a special circuit that checks communication signals, voltage, and compressor rotation speed. Recommended parts: connection wires, IPM module board, outdoor fan assembly, compressor, outdoor PCB.
Applies to: D5FUHA
Likely causes
- Wiring fault between PCB and compressor
- Faulty IPM board
- Outdoor fan or ventilation problem
- Compressor winding fault
- Faulty outdoor PCB
Test and repair steps
- Check the wiring between the PCB and the compressor. Ensure proper connections or replace wires and connectors if improperly wired.
- Check the IPM. If it is not functioning properly, replace the IPM board or the outdoor PCB.
- Check the outdoor fan and outdoor unit ventilation. If not functioning properly, see Fan Speed Malfunction (EH03/EC 07).
- Check the compressor resistance. If out of acceptable range, replace the compressor.
- If the compressor is within range, replace the outdoor PCB.
Other codes on the same units
- PC 00 Outdoor IPM module protection
- PC 01 Outdoor voltage protection
- PC 02 Compressor top or IPM temperature protection
- PC 03 High or low pressure protection
- PC 06 Quick maintenance code (outdoor)
- PC 08 Quick maintenance code (outdoor)
- PC 0F Quick maintenance code (outdoor)
- PC 0a Quick maintenance code (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUHA service manual, p. 32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.