PC 03 High or low pressure protection

High severity D5FUHA

What the control is telling you

The outdoor pressure switch stops the system when high pressure is above 4.4 MPa or low pressure is below 0.13 MPa. The LED shows this code. Prepare connection wires, pressure switch, outdoor fan, outdoor main PCB, and refrigerant.

Applies to: D5FUHA heat pump outdoor unit

Likely causes

  • High pressure: dirty outdoor heat exchanger, poor outdoor ventilation, outdoor fan not running properly, high outdoor ambient above 50°C, faulty high pressure protector, wiring fault
  • Low pressure: low refrigerant charge, high pressure valve not fully open, indoor fan not running properly in cooling, very low outdoor ambient, faulty low pressure protector, wiring fault

Test and repair steps

  1. High pressure check that the high pressure switch and main board are wired correctly. Disconnect the plug and measure the protector resistance. A good protector reads 0 as printed in the manual. Replace the protector if it is open.
  2. High pressure check outdoor ambient. If it is above 50°C, check outdoor ventilation.
  3. High pressure clean the outdoor heat exchanger if it is dirty.
  4. High pressure check that the outdoor fan runs properly. If the fan speed is out of range, follow the fan speed procedure.
  5. High pressure if the fault remains after these checks, replace the outdoor main board.
  6. Low pressure check that the low pressure protector and main board are wired correctly. Reconnect if needed.
  7. Low pressure measure the low pressure protector resistance. A good protector reads 0 as printed in the manual. Replace it if it is open.
  8. Low pressure if ambient is too low, stop the unit and address the cause.
  9. Low pressure fully open the high pressure valve core.
  10. Low pressure check that the indoor fan runs properly in cooling mode. If the fan speed is out of range, follow the fan speed procedure.
  11. Low pressure check the refrigerant system. If refrigerant is low, add refrigerant and confirm normal operation.
  12. Low pressure if the fault remains, replace the outdoor main board.

Other codes on the same units

  • PC 00 Outdoor IPM module protection
  • PC 01 Outdoor voltage protection
  • PC 02 Compressor top or IPM temperature protection
  • PC 04 Inverter compressor drive error
  • PC 06 Quick maintenance code (outdoor)
  • PC 08 Quick maintenance code (outdoor)
  • PC 0F Quick maintenance code (outdoor)
  • PC 0a Quick maintenance code (outdoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier D5FUHA Service Manual, p. 33-34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.