Rinnai · Air handler · Other

Continuous fan

Canadian Hydronic Air Handler

What happens, in order

  1. Thermostat closes R to G with no heat or cool call
  2. Blower runs at the continuous-fan airflow
  3. Blower stops when the fan switch is released

Applies to: Rinnai Canadian hydronic air handler (heat pump and A/C versions)

Models

Canadian air handler

More Rinnai air handler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai Canadian Hydronic Air Handler Installation and Operation Manual (600000023), thermostat operation section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.