Rinnai · Air handler · Pump/purge
Circulating pump exercise
What happens, in order
- Control watches time since the pump last ran
- Once every 24 hours it completes the R to W circuit by itself
- Hot water circulating pump runs for one minute
- Pump goes back to idle until the next heating call or exercise
Timings and thresholds
| Item | Value |
|---|---|
| Pump run time | 1 min |
| Exercise interval (default) | 24 h |
Applies to: Rinnai Canadian hydronic air handler (heat pump and A/C versions)
Models
More Rinnai air handler sequences
- Heating call, single-stage thermostat · Heating
- Heating call, two-stage thermostat · Heating
- Cooling call, single-stage thermostat · Cooling
- Cooling call, two-stage thermostat · Cooling
- Continuous fan · Other
Related
Rinnai error codes · Rinnai tips · Rinnai parts · All Rinnai sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rinnai Canadian Hydronic Air Handler Installation and Operation Manual (600000023), thermostat operation section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.