Rinnai · Air handler · Pump/purge

Circulating pump exercise

Canadian Hydronic Air Handler

What happens, in order

  1. Control watches time since the pump last ran
  2. Once every 24 hours it completes the R to W circuit by itself
  3. Hot water circulating pump runs for one minute
  4. Pump goes back to idle until the next heating call or exercise

Timings and thresholds

ItemValue
Pump run time1 min
Exercise interval (default)24 h

Applies to: Rinnai Canadian hydronic air handler (heat pump and A/C versions)

Models

Canadian air handler

More Rinnai air handler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai Canadian Hydronic Air Handler Installation and Operation Manual (600000023), thermostat operation section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.