Gree · Mini-split · Heating

Heating mode

Sapphire

What happens, in order

  1. Room temperature is at or below the set temperature plus 2C (3.6F), so the compressor, outdoor fan and reversing valve energize and the indoor fan runs under the anti-cold-air rules
  2. Between set temperature plus 2C and plus 5C (9F), the unit keeps its previous state
  3. At set temperature plus 5C or higher, the compressor stops, the outdoor fan runs on 30 s and the indoor fan blows residual heat on low for 60 s with the speed locked
  4. When the unit is switched off or changed to another mode, the reversing valve is de-energized after the compressor has stopped
  5. Compressor frequency is adjusted automatically with outdoor temperature
  6. With the compressor running and outdoor air at 20C (68F) or above, a low or medium indoor fan speed is raised to high; at 18C (64.4F) or below it returns to the set speed

Timings and thresholds

ItemValue
Set temperature range16-30C (68-86F)
Start pointSet temperature plus 2C
Stop pointSet temperature plus 5C
Residual heat blow60 s low speed
Outdoor fan run-on30 s

Applies to: Gree Sapphire wall mini-split heat pumps

Models

SAP09HP230V1ASAP12HP230V1ASAP18HP230V1ASAP24HP230V1A

More Gree mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gree Sapphire 9-12k service manual (SAP09-12HP230V1A), Technical Information - Function and Control; Gree Sapphire 18-24k service manual (SAP18-24HP230V1A), same section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.