Gree · Mini-split · Cooling

Cooling mode

Sapphire

What happens, in order

  1. Room temperature is at or above the set temperature, so the compressor and outdoor fan start and the indoor fan runs at the selected speed
  2. Reversing valve stays de-energized in cooling
  3. When the room falls 2C (3.6F) below the set temperature, the compressor stops, the outdoor fan runs on for 30 s and the indoor fan keeps its set speed
  4. Between set temperature minus 2C and set temperature, the unit keeps doing whatever it was doing
  5. While the compressor runs and the room is within 2C below setpoint, a high indoor fan speed drops to medium; it returns to the set speed once the room is 1C (1.8F) above setpoint
  6. Overcurrent high total current limits compressor frequency; excessive current stops the compressor, the outdoor fan runs on for 30 s and E5 is shown on the indoor unit (outdoor yellow light blinks 5 times)

Timings and thresholds

ItemValue
Set temperature range16-30C (68-86F)
Outdoor fan run-on after compressor stop30 s
Stop pointSet temperature minus 2C (3.6F)

Codes you may see during this

E5

Applies to: Gree Sapphire wall mini-split heat pumps

Models

SAP09HP230V1ASAP12HP230V1ASAP18HP230V1ASAP24HP230V1A

More Gree mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gree Sapphire 9-12k service manual (SAP09-12HP230V1A), Technical Information - Function and Control; Gree Sapphire 18-24k service manual (SAP18-24HP230V1A), same section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.